Prony Analysis -A Case Study in Eastern Regional Power System in India
DOI:
Keywords:
Linear state estimation, Low-frequency oscillations, PMU, Prony analysis, Small-signal stability, Synchrophasor technology, WAMSAbstract
The stability of the Indian power grid is frequently challenged by Low-Frequency Oscillations (LFOs), particularly in the hydro-dominant Eastern Region, where evacuation corridors are constrained. This paper presents a detailed analysis of a cascade tripping event that occurred on July 7, 2017, involving the 400 kV Teesta-III to Rangpo corridor. Utilizing high-resolution synchro phasor data obtained from Phasor Measurement Units (PMUs), this study characterizes the oscillatory behavior of the grid during the disturbance. While conventional Fast Fourier Transform (FFT) methods are often employed for spectral monitoring, this work employs Prony Analysis due to its superior capability in analyzing non-stationary, transient signals and its ability to directly extract modal damping ratios. The analysis identifies the dominant inter-area and local modes, quantifying their energy, damping percentage, and frequency content. The results demonstrate that specific modes exhibited insufficient damping during the event, contributing to system separation. These findings are subsequently used to derive necessary control parameters for the design of robust Power System Stabilizers (PSS) and oscillation damping filters, aimed at enhancing the dynamic stability of the Eastern Regional Grid.
References
C. Liu (1998) A discussion of the WSCC 2 July 1996 outage. 18(10), 60-61.
(2004) Final Report on the August 14, 2003 Blackout in United States and Canada.
A. Andersson, P. Donalek, R. Farmer (2005) Causes of the 2003 major grid blackouts in North America and Europe, and recommended means to improve system dynamic performance. 20(4), 1922-1928.
M. Donolo Advantages of synchro phasor measurements over SCADA measurements for the power system state estimation. (LAN2006-10).
M. Mynam, A. Harikrishna, V. Singh (2011) Synchro phasors Redefining SCADA Systems.
M. Sufyan, M. Zuhaib, M. Sefid, M. Rihan (2018) Analysis of Effectiveness of PMU based Wide Area Monitoring System in Indian Power Grid.
S. Soni, S. Bhil, D. Mehta, S. Wagh (2012) Linear state estimation model using Phasor Measurement Unit (PMU) technology.
M. Hurtgen, J.-C. Maun Advantages of power system state estimation using Phasor Measurement Units. https://www.researchgate.net/publication/228892103-lseadv
P. Ray (2016) Power system low frequency oscillation mode estimation using wide area measurement systems. https://doi.org/10.1016/j.jestch.2016.11.019
S. Chitturi, S. Chakrabarti, S. Singh (2014) Comparing performance of Prony analysis and Matrix pencil method for monitoring power system oscillations. 1-6.
D. Wadduwag, U. Annakkage, K. Narendra (2015) Identification of dominant low-frequency modes in ring-down oscillations using multiple Prony models. 1-9.
V. Rampurkar, F. Kazi, H. Mangalvedekar, P. Pentayya, C. Kumar, R. A. (2013) PMU Based Identification of Low Frequency Oscillations - A Case Study.
P. Dalawai, V. Pandey (2013) Application of synchrophasors - A case study in northern regional power system in India. https://www.researchgate.net/publication/289491655-prony
P. Puviya, N. Priyadarshini (2017) State estimation in power system using weighted least squares method. 1-6.
Downloads
Published
Issue
Section
License
Copyright (c) 2025 Authors and Global Journals Private Limited

This work is licensed under a Creative Commons Attribution 4.0 International License.